Glow Brand Boiler: 0-10 VDC input to modulate firing rate (Mode 5)
0-10 VDC input to modulate firing rate (Mode 5) on a Glow Brand boiler: Mode 5 on the C95 and C140 combis, a 0-10 VDC input driving the firing rate. It works like Mode 4. The boiler needs at least 2 VDC to wake up, and at 2 VDC the display reads 1%, which is minimum fan RPM. At 10 VDC you get 100%, maximum fan RPM, and everything between follows the signal proportionally. When the rate looks wrong, I put a meter on the signal before blaming the boiler.
Applies to: C95 & C140 combi boilers
Common causes of 0-10 vdc input to modulate firing rate (mode 5)
- Control signal below 2 VDC, so the boiler never activates
- Wrong polarity or loose terminal on the 0-10 VDC input
- External controller output not scaled to the full 0-10 VDC range
How to fix 0-10 vdc input to modulate firing rate (mode 5): step by step
- Apply at least 2 VDC to activate the boiler.
- Confirm the display reads 1% at 2 VDC (minimum fan RPM).
- Confirm the display reads 100% at 10 VDC (maximum fan RPM).
- Measure the signal at the boiler terminals with a DC meter, not at the controller.
- Check that the firing rate follows the signal between those points.
If the unit shows an error code, look it up: Glow Brand Boiler codes
Source: Glow Brand C95 & C140 manual, p. 64. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.