General: Purge runs > 2–3 minutes per cycle
Purge runs > 2–3 minutes per cycle on a general: On a low-pressure chiller with a purge unit, the purge running more than 2 to 3 minutes per cycle is a warning that air is getting into the vacuum side. Noncondensables cut capacity, and moisture that gets in forms acid, so don't ignore it. Work only with the machine's procedure, and have a qualified chiller tech handle the refrigerant.
Common causes of purge runs > 2–3 minutes per cycle
- Air leak into the vacuum side
- Noncondensables reducing capacity
- Moisture forming acid inside the system
How to fix purge runs > 2–3 minutes per cycle: step by step
- Log the purge run time per cycle and watch the trend
- Leak search the low-pressure side per the machine's procedure
- Repair the leak
- Purge out the noncondensables
- Recheck that purge time returns to normal
- Check oil for moisture or acid if the leak was large
If the unit shows an error code, look it up: Navien General codes Trane General codes
Source: General HVAC service practice — verify per model. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.