General: Oil foaming at start
Oil foaming at start on a general: Oil foams at startup. Refrigerant has migrated into the oil sump and boils out when the compressor starts. Pressure drops, refrigerant flashes, oil turns to foam, and the bearings may be starved for a moment.
Common causes of oil foaming at start
- Refrigerant migration to the sump
- Crankcase heater failed or not on long enough
- Liquid leaking past the metering device on the off cycle
- Compressor sitting in a cold space
How to fix oil foaming at start: step by step
- Confirm the sump heater is working and has been on long enough.
- Run at reduced load until the foaming clears.
- Check the oil level once it settles.
- If it repeats every start, look into why refrigerant keeps migrating.
- Check the metering device and solenoid for leak-through.
If the unit shows an error code, look it up: Navien General codes Trane General codes
Source: General HVAC service practice — verify per model. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.