General: Noisy ductwork
Noisy ductwork on a general: Noisy ductwork usually isn't the duct's fault. What I usually find is somebody sped the blower up to cover for undersized equipment or duct, and now the air is roaring through the system. Sort out the cause of the noise first, since the fix depends on whether it is air rushing, metal panels flexing or a rumbling fan.
Common causes of noisy ductwork
- Velocity over 700 fpm because the blower was sped up to cover undersized equipment or duct
- Sharp edges in the grille or duct
- Vibrating panels, called oil-canning
- Fan or motor rumble
- Expansion popping as the duct heats and cools
How to fix noisy ductwork: step by step
- Remove the grille and listen to see if the noise stops
- Measure the velocity at the problem section
- Lower the velocity by reducing blower speed if the system allows, or by enlarging the duct
- Fit vaned or long-radius elbows
- Line or wrap the duct, and cross-break flat panels
- Add a fabric joint at the furnace and an acoustic chamber if needed
If the unit shows an error code, look it up: Navien General codes Trane General codes
Source: General HVAC service practice — verify per model. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.