General: No heating
No heating on a general: What I usually find on a zoned no-heat call is a panel or damper issue masking an ordinary furnace call. The furnace can't run if the panel never sends W, so I settle that before I touch the furnace. Once I see 24 V on W to C at the system side, the problem is in the furnace itself.
Common causes of no heating
- Zone stats not calling or wired incorrectly
- Dampers not opening after the call
- Panel output not sending W to the furnace
- Furnace itself not responding to a good call
How to fix no heating: step by step
- Set all stats to heat 5°F above room and let the dampers all open after the minimum delay
- On the stat side, expect 0 V R to W, 24 V R to Y and 24 V R to C
- On the system side, expect 24 V W to C, 0 V Y to C and 24 V R to C
- No W at the system side means a panel or stat problem
- If there's 24 V W to C and no heat, move to the furnace for ignition, gas flow, safeties and pressure switches
- Gas and ignition faults are a job for a licensed tech
If the unit shows an error code, look it up: Navien General codes Trane General codes
Source: General HVAC service practice — verify per model. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.