General: Low capacity
Low capacity on a general: Low capacity on an absorption-type unit usually means something upstream is working against it, not that the machine has quit. Before touching anything, confirm what the condenser is seeing and what the chilled water set point is. Pressure readings on these systems have to be taken with the right gauges, and the charge is a job for a qualified technician.
Common causes of low capacity
- High condenser entering air temperature cutting into capacity
- Chilled water set point set too low (see the A24 table in the manual)
- Wrong solution charge or off-spec system pressures
How to fix low capacity: step by step
- Confirm the power is locked out before connecting or moving any gauges
- Use a steel gauge manifold only, because standard brass fittings are not suited to this system
- Verify the high side reads about 200 to 300 psig and the low side about 40 to 60 psig
- Compare the chilled water set point against the A24 table and correct it if it's out of range
- Check the condenser entering air temperature and clear any recirculation or blockage
- If pressures are off, have a licensed tech correct the water, inhibitor and NH3 amounts rather than guessing at the charge
If the unit shows an error code, look it up: Navien General codes Trane General codes
Source: General HVAC service practice — verify per model. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.