Electrical: Fuse blows / breaker trips repeatedly
Fuse blows / breaker trips repeatedly on a electrical: A fuse that blows or a breaker that trips over and over is telling you something, and the thing I usually find first is the wrong fuse in the holder. A fast-acting fuse on a compressor will pop on every start because of the inrush. After that it is a short, or the motor is overloaded. Don't just keep putting bigger fuses in.
Common causes of fuse blows / breaker trips repeatedly
- Wrong fuse rating or type for the motor, such as a fast-acting fuse on a compressor
- Short in the circuit
- Motor overload
How to fix fuse blows / breaker trips repeatedly: step by step
- Turn the power off and lock it out before you touch anything
- Confirm the rating against the motor fuse table (A21) and the UL nameplate
- Use time-delay fuses on compressors
- If the rating is correct, hunt for a short with a meter
- On a breaker, examine its capacity; if it is adequate, there is a short or other trouble
- For anything beyond simple checks, call a licensed electrician or technician
Source: General HVAC service practice — verify per model. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.