Daikin Water Heater: Transmission wiring layout and three-way valve circuit
Transmission wiring layout and three-way valve circuit on a Daikin water heater: Up to six Mega-Q systems can share one water loop. Up to eight Mega-Q systems can be run from one tank controller kit. The tank control board's three-way valve circuit sends a defrost/freezing prevention signal. Its contact is a no-voltage contact rated 208/230 V, 10 mA to 2 A.
Applies to: Mega-Q multi-unit systems
How to fix transmission wiring layout and three-way valve circuit: step by step
- Never connect power supply wiring to the transmission terminal.
- Wire the tank control board, heat source and cascade units per the transmission wiring diagram.
- For a closed hot water storage tank, connect the three-way valve circuit between X1 and X2 of the X1M terminal on the cascade unit board A7P.
- Limit each water loop to six Mega-Q systems and each tank controller kit to eight systems.
If the unit shows an error code, look it up: Daikin Water Heater codes
Source: Daikin Mega-Q installation manual, p. 27. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.