Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Daikin Water Heater: Release air from cascade unit water piping

Updated · by Aurora Star Tech Inc.

Release air from cascade unit water piping on a Daikin water heater: Purge air from the water side of the cascade unit before test operation.

Homeowner with a heating or cooling system problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Cascade unit water side

Common causes of release air from cascade unit water piping

  • Air trapped in the circulating or hot water piping

How to fix release air from cascade unit water piping: step by step

  1. Open the lower front panel of the cascade unit.
  2. Open the gate valves on the circulating and hot water piping between the cascade and the storage tank so water can flow through the unit.
  3. Open both air release valves until only water comes out of the hose, then close the valves.
  4. Close the front panel when finished.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Daikin Water Heater codes

Source: Mega-Q installation manual, p. 41. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency HVAC Service

647-657-2977