Daikin Water Heater: Power supply and ground wire termination
Power supply and ground wire termination on a Daikin water heater: Ground must be connected before power and disconnected after power. Terminals must not take strain from the wiring.
Applies to: Mega-Q power and ground wiring
How to fix power supply and ground wire termination: step by step
- Fit insulation sleeves to the power wiring before connecting it.
- Use round crimp style terminals and insulate the crimp with a sleeve.
- Connect the ground wire before the power wire, leaving enough slack so power is tightened before ground if the line pulls loose.
- Route the ground wire through the notch in the cup-style washer so no other wire is pinched.
- When two wires share one terminal, place the thinner wire on top and clamp both to the resin hook.
- Do not solder stranded wire before use.
- Ground all wiring per local and national code.
If the unit shows an error code, look it up: Daikin Water Heater codes
Source: Daikin Mega-Q installation manual, p. 29. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.