Daikin Water Heater: Operate the stop valve
Operate the stop valve on a Daikin water heater: Do not open the stop valve until all checks in the checking equipment and installation status section are done. Leaving it open with power off can let refrigerant condense in the compressor. Use a dedicated tool. The 1/2 in. liquid valve is not back-seal type, so do not force it. The 1 in. gas valve is front and back seal type.
Applies to: Heat source unit stop valves (RXHWQ120MQTJA)
How to fix operate the stop valve: step by step
- Remove the stop valve cover.
- To open: insert a hexagon wrench and turn counterclockwise until the shaft stops (1/2 in.) or until the shaft stops and the designated torque is reached (1 in.).
- To close: turn clockwise until the shaft stops at the designated torque.
- Tighten the stop valve cover to the designated torque.
- Check for refrigerant leaks after tightening the cover.
- When working on the service port, use a charge hose with a valve depressor pin because it is a Schrader valve. Tighten the port cover and check for leaks.
If the unit shows an error code, look it up: Daikin Water Heater codes
More commissioning tips for water heater
Source: Daikin Mega-Q installation manual, p. 51. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.