Daikin Water Heater: Heat source unit knockout and conduit entry
Heat source unit knockout and conduit entry on a Daikin water heater: Power and transmission lines use separate knockouts on the front lower plate. Transmission runs on the left knockout. Hole sizes shown in the manual are 7/8 in (22.2 mm), 1-1/8 in (27.8 mm) and 1-3/8 in (34.5 mm).
Applies to: Mega-Q heat source unit
How to fix heat source unit knockout and conduit entry: step by step
- Choose a knockout whose size suits the conduit for the power and ground conductors.
- Use the left knockout (7/8 in / 22.2 mm) for transmission wiring in conduit.
- Remove burrs around the knockout holes.
- Protect the wiring with tape where it passes through.
If the unit shows an error code, look it up: Daikin Water Heater codes
Source: Daikin Mega-Q installation manual, p. 26. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.