Daikin Water Heater: Drainage and freeze protection on site
Drainage and freeze protection on site on a Daikin water heater: Water drains from the bottom frame during operation and defrost. Cold outdoor temperatures can freeze the bottom frame and foundation.
Applies to: Heat source unit and cascade unit
Common causes of drainage and freeze protection on site
- Condensation and defrost water drop through gaps in the bottom frame.
- Ground below freezing for long periods can freeze the bottom frame.
How to fix drainage and freeze protection on site: step by step
- If drain water is a problem, use a stand and a field supplied drain pan.
- In areas that stay below freezing for long periods, attach a drain pan heater (sold separately) to the heat source unit.
- Leave a gap between the bottom frame and the foundation surface so frozen ground does not reach the frame. In cold regions the manual recommends 20 in. (500 mm) to 40 in. (1000 mm).
- Provide a drainage ditch around the foundation so water does not collect around the system.
- In areas where the outdoor air can drop below freezing, drain the water from inside the cascade unit before switching off the breaker.
- Do not turn off the power immediately after stopping operation. Wait at least 5 minutes before switching off the power, or water leakage can occur.
If the unit shows an error code, look it up: Daikin Water Heater codes
Source: Daikin Mega-Q installation manual, p. 9-10. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.