Daikin Water Heater: Check phase balance and phase rotation
Check phase balance and phase rotation on a Daikin water heater: Voltage imbalance above 2 percent shortens unit life. Above 4 percent the unit shuts down and a malfunction code shows on the remote controller. Reverse phase stops normal operation.
Applies to: Mega-Q three-phase power supply
Common causes of check phase balance and phase rotation
- Voltage imbalance above 2 percent
- Voltage imbalance above 4 percent triggers shutdown
- Reverse phase connection
How to fix check phase balance and phase rotation: step by step
- Measure the phase-to-phase voltage balance; it must be 2 percent or less.
- If the imbalance exceeds 4 percent, the unit will shut down; correct the supply before restarting.
- If the phase order is wrong, swap two of the three phases.
- If reverse-phase, lost phase, momentary blackout or on/off cycling is possible, fit a local reverse-phase protection circuit.
If the unit shows an error code, look it up: Daikin Water Heater codes
Source: Mega-Q installation manual, p. 55. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.