Daikin Heat Pump: Wiring the thermostat to a communicating indoor unit and outdoor unit
Wiring the thermostat to a communicating indoor unit and outdoor unit on a Daikin heat pump: Use 18-gauge wire, keep the run under 125 feet, and confirm voltage before and after wiring. The communication bus should read 0.6 VDC between Data 1 and Data 2. Wrong wiring causes a communication error or the equipment will not be recognized.
Applies to: Communicating indoor and outdoor systems
Common causes of wiring the thermostat to a communicating indoor unit and outdoor unit
- Wire run longer than 125 feet
- Thermostat terminals 1, 2, C and R wired to the wrong indoor terminals
- Indoor wires 1 and 2 not matched to outdoor 1 and 2
How to fix wiring the thermostat to a communicating indoor unit and outdoor unit: step by step
- Check voltage before wiring.
- Run 18-gauge wire, no longer than 125 feet, between the thermostat and the indoor unit.
- Connect thermostat 1, 2, C and R to indoor unit 1, 2, C and R.
- Connect indoor unit wires 1 and 2 to outdoor unit 1 and 2.
- Check for 0.6 VDC between Data 1 and Data 2.
- Check voltage again after wiring is complete.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin One Touch installation guide, p. 14. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.