Daikin Heat Pump: Using the 4-pin connectors on communicating equipment
Using the 4-pin connectors on communicating equipment on a Daikin heat pump: Communicating indoor and outdoor units use a supplied 4-pin connector. Indoor units match R, C, 1 and 2 on the 4-pin to the indoor board. Outdoor units match 1 and 2 on the 4-pin to the outdoor board. The thermostat is labeled 1, 2, C and R, and wrong wiring gives a communication error or unrecognized equipment.
Applies to: Communicating indoor and outdoor units
Common causes of using the 4-pin connectors on communicating equipment
- 4-pin connector wired to the wrong board terminals
- Thermostat labels 1, 2, C, R not matched to the equipment
How to fix using the 4-pin connectors on communicating equipment: step by step
- Match R, C, 1 and 2 on the indoor 4-pin connector to the same terminals on the indoor board.
- Match 1 and 2 on the outdoor 4-pin connector to the outdoor board.
- Confirm the thermostat 1, 2, C and R wires land on the matching terminals.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin One Touch installation guide, p. 15. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.