Daikin Heat Pump: Three-step nitrogen system pressure test
Three-step nitrogen system pressure test on a Daikin heat pump: Recommended pressure test once all refrigerant line connections are complete. Each step holds pressure to check for drops. Any drop means finding and repairing the leak, then repeating from step 1.
Applies to: DX6VS / DZ6VS / DZ6VSA outdoor units
How to fix three-step nitrogen system pressure test: step by step
- Pressurise with nitrogen to 150 PSIG and hold for 3 minutes.
- Pressurise with nitrogen to 325 PSIG and hold for 5 minutes.
- Pressurise with nitrogen to 450 PSIG and hold for 4 hours.
- If any pressure drop occurs at any step, locate and repair the leak and repeat from step 1.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin DX6VS/DZ6VS installation manual (3P731493-1), p. 17. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.