Daikin Heat Pump: Testing thermistors

Updated · by Aurora Star Tech Inc.

Testing thermistors on a Daikin heat pump: Factory sensors on outdoor units and EEV indoor units are: Ta (outdoor air), Tm (outdoor coil), Tl (outdoor liquid), Td (discharge), Tb (coil defrost), Ts (suction), Tgi (indoor gas) and Tli (indoor liquid). Compare readings against the resistance table in the manual.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Outdoor unit and EEV indoor unit thermistors

Common causes of testing thermistors

  • Open thermistor
  • Shorted thermistor
  • Resistance outside valid range

How to fix testing thermistors: step by step

  1. Disconnect power to all equipment.
  2. Unplug the thermistor connector from the control board.
  3. Connect an ohmmeter across the thermistor terminals.
  4. Compare the reading with the thermistor resistance and temperature table.
  5. Replace the thermistor if it is open, shorted, or outside the valid resistance range.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Daikin Heat Pump codes

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 21. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.