Updated · by Aurora Star Tech Inc.

Test inverter capacitor DC voltage before servicing on a Daikin heat pump: Check the DC voltage on the inverter capacitor before touching the control board or wiring. Discharge first, then confirm the voltage is low.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: 1.5 - 5.0 ton outdoor units (1.5-3.0 ton and 3.5-5.0 ton diagrams)

How to fix test inverter capacitor dc voltage before servicing: step by step

  1. Turn off power and wait at least 10 minutes for the capacitor to discharge.
  2. Set the multimeter to DC voltage range.
  3. Measure across the capacitor terminals C+ and C-.
  4. Confirm the reading is 50 V DC or less before working on the board.
  5. Do not work on the capacitor or board if the reading is above 50 V DC. Discharge it first.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Daikin Heat Pump codes

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EA, p. 5-6. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.