Updated · by Aurora Star Tech Inc.

Signal transmission error code U4 on a Daikin heat pump: Indoor and outdoor units are not receiving valid signal data from each other.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Inverter pair wall mounted FTXM-W/V, indoor to outdoor communication

Common causes of signal transmission error code u4

  • Power supply voltage out of specification
  • Voltage drop on the supply
  • Wiring error between indoor and outdoor units
  • Broken indoor-outdoor connection wire (wire No. 3)
  • Defective outdoor unit PCB
  • Short circuit in the fan motor winding
  • Defective indoor unit PCB
  • Disturbed power supply waveform

How to fix signal transmission error code u4: step by step

  1. Turn off the power switch before connecting or disconnecting any connector.
  2. Check the power supply waveform for disturbance. Refer to Check No. 11 (P.142).
  3. Measure the voltage on the indoor terminal board between No. 1 and No. 3, and between No. 2 and No. 3.
  4. Check LED A on the outdoor unit PCB. If it blinks, continue to the wiring checks. If it stays continuously on or off, follow the fault path for the outdoor PCB.
  5. Check the indoor-outdoor connection wires for wiring errors, insulation and damage.
  6. Correct any wiring error found.
  7. Replace the connection wires if they are damaged or broken.
  8. If there is power supply disturbance, locate its cause and correct it.
  9. If the indoor terminal voltage is wrong, replace the indoor unit PCB (control PCB).
  10. If the outdoor PCB shows the fault, replace the outdoor unit PCB (main PCB).
  11. Check the supply voltage and correct it if out of range.
  12. Rotate the outdoor fan by hand. If it does not turn smoothly, or voltage fluctuation is outside ±10%, replace the outdoor fan motor and outdoor unit PCB.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Daikin Heat Pump codes

Source: Daikin FTXM-W/V service manual SiUS042113EA, p. 113. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.