Daikin Heat Pump: S-4 Checking transformer and control circuit
S-4 Checking transformer and control circuit on a Daikin heat pump: The indoor unit has a step-down transformer (208/230 or 115 V primary to 24 V secondary). The outdoor unit has no transformer.
Applies to: Indoor unit transformer, EEV air handler
Common causes of s-4 checking transformer and control circuit
- No secondary voltage: faulty transformer, bad wiring or bad splices
- Line voltage missing at the primary
How to fix s-4 checking transformer and control circuit: step by step
- Disconnect all power before servicing.
- Remove the control panel cover to access the transformer.
- With power on, use a voltmeter to check voltage across the transformer secondary (R to C).
- If there is no voltage, check the transformer primary voltage at the incoming line voltage connections or splices.
- If line voltage is present at the primary and the wiring and splices are good, replace the transformer.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin DX6VS / DZ6VS service instructions SiUS612209EA, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.