Daikin Heat Pump: S-1 Checking voltage
S-1 Checking voltage on a Daikin heat pump: Check supply voltage before servicing the control circuit or components.
Applies to: DX6VS / DZ6VS outdoor units and indoor units
Common causes of s-1 checking voltage
- No reading at line voltage: open wiring, open fuse, no power, or a fault from the unit to the fused disconnect.
How to fix s-1 checking voltage: step by step
- Remove the outer case and control panel cover from the unit being tested.
- With power on, use a voltmeter to measure across L1 and L2 at the outdoor unit, or at the field connections for indoor units or heaters.
- If there is no reading, repair the open wiring, fuse, or supply as needed.
- With ample voltage at the line voltage connectors, energize the unit.
- Compare readings with the supply voltage limits table.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin DX6VS / DZ6VS service instructions SiUS612209EA, p. 15. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.