Removing pinch piping from the heat source unit on a Daikin heat pump: Pinch piping must be vented before it is removed, otherwise the stop valve can rupture or residual oil can catch fire.
Applies to: Heat source unit stop valve connections
How to fix removing pinch piping from the heat source unit: step by step
- Remove the valve cover and check that the stop valve is fully closed.
- Connect a charge hose with push rod to the service port and check for no residual pressure.
- Cut the small pinch piping with a piping cutter so a cross section opens. Confirm again there is no residual pressure.
- Leave the pipe until the oil runs out.
- Remove the large pinch piping.
- Drain all gas and oil from the pinch piping before removing it.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin Mega-Q installation manual, p. 18. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.