Daikin Heat Pump: Remove the electrical box and main control board
Remove the electrical box and main control board on a Daikin heat pump: Access the main control board on 3.5 to 5.0 ton units. Some connectors are HP models only.
Applies to: 3.5 to 5.0 ton HP and AC models
How to fix remove the electrical box and main control board: step by step
- Remove the 2 screws and the refrigerant cooling pipe jacket cover.
- Remove the 2 screws and the electrical box. Detach the HPS connectors.
- Disconnect all connectors on the main control board: EEV coil (X21A), thermistors (X12A), HPS (X32A), four way valve coil (X25A, HP only), solenoid valve coil (X28A, HP only), power supply (L1, L2), OL (X33A) and ground (E1, E3).
- Remove the 11 screws, then remove the main control board and insulation sheet.
- Torque the jacket cover screws and apply grease as specified on reassembly.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin SiUS612209EA service instructions, p. 116, 117. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.