Daikin Heat Pump: Remove panels, grille and rear plate (1.5 to 3.0 ton outdoor units)
Remove panels, grille and rear plate (1.5 to 3.0 ton outdoor units) on a Daikin heat pump: Panel and cover removal for 1.5 to 3.0 ton heat pump and AC outdoor units. Reassemble in reverse order.
Applies to: 1.5 to 3.0 ton HP and AC outdoor units
How to fix remove panels, grille and rear plate (1.5 to 3.0 ton outdoor units): step by step
- Remove the 8 screws and take off the right side panel.
- Remove the 4 screws and take off the top panel.
- Remove the 5 screws and take off the front panel. When reassembling, hook the front panel into the slit of the partition plate.
- Remove the 4 screws and take off the discharge grille.
- Cut the 2 clamps, then remove the 3 terminal block screws (1 M5 x 12 and 2 M4 x 10). Disconnect the external power, ground and communication wires from the terminal block.
- Remove the 7 screws and take off the rear plate.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EA, p. 81-83. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.