Daikin Heat Pump: Remove heat exchanger, heat pump 3.5 to 5.0 ton
Remove heat exchanger, heat pump 3.5 to 5.0 ton on a Daikin heat pump: Heat pump models only. The heat exchanger is removed after the rear cover and brazed joints, then the partition plate.
Applies to: DX6VS / DZ6VS heat pump outdoor units, 3.5 to 5.0 ton
How to fix remove heat exchanger, heat pump 3.5 to 5.0 ton: step by step
- Remove the 3 screws and take off the rear cover.
- Protect nearby putty, terminal cover and plastic parts from the brazing flame, and shield with a steel plate or protective sheet.
- Heat the brazed heat exchanger joints and disconnect them. The 5.0 ton model is shown as the representative drawing.
- Remove the 3 screws and take off the heat exchanger.
- On a 4 screw model, remove the 4 screws and the partition plate. On a 3 screw model, remove the 3 screws and the partition plate.
- When reassembling the partition plate, insert the hook of the bottom frame into the slit of the partition plate.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EA, pp. 124 to 125. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.