Daikin Heat Pump: Remove fan, fan motor and fan motor stand (1.5 to 3.0 ton)
Remove fan, fan motor and fan motor stand (1.5 to 3.0 ton) on a Daikin heat pump: Fan and fan motor removal for 1.5 to 3.0 ton outdoor units. Route the fan motor lead correctly on reassembly.
Applies to: 1.5 to 3.0 ton HP and AC outdoor units
How to fix remove fan, fan motor and fan motor stand (1.5 to 3.0 ton): step by step
- Remove the 1 screw and take off the drip proof cover. Unhook the fan motor lead from the drip proof cover hook.
- Cut the clamp and disconnect the fan motor connector (X200A).
- Remove the M8 nut and take off the fan.
- Remove the 2 screws and take off the fan motor stand.
- Remove the 4 M5 x 25 hex head tapping screws and take off the fan motor.
- On reassembly, bend the 2 claws of the fan motor stand and fix the lead wire.
- On reassembly, route the fan motor lead through the hole in the stand (required on 2.5/3.0 ton), keep the lead downward, and leave no slack.
- On 1.5/2.0 ton units, clamp the compressor lead wires about 20 to 50 mm from the end of the fan motor lead protective tube and keep them free of tension.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EA, p. 84-87. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.