Daikin Heat Pump: Remove compressor, heat pump 3.5 to 5.0 ton (overload and brazed piping)
Remove compressor, heat pump 3.5 to 5.0 ton (overload and brazed piping) on a Daikin heat pump: Heat pump models only. Covers the last steps of compressor removal: overload (OL) and brazed piping. Steps 1 to 5 are on the previous page and are not in this extract.
Applies to: DX6VS / DZ6VS heat pump outdoor units, 3.5 to 5.0 ton
How to fix remove compressor, heat pump 3.5 to 5.0 ton (overload and brazed piping): step by step
- Remove the OL. When reassembling, fit the retainer first: insert its lower hooks into the square holes of the fixture, then push the upper hooks until they latch in the square holes.
- Route the OL lead wire through the harness path as shown in the manual.
- Protect the area first: remove putty, the terminal cover and any plastic parts that could burn, and place a protective sheet or steel plate so the brazing flame cannot reach nearby parts.
- Heat the brazed compressor piping joints and disconnect them. Keep the pipe-cutting angle within the 45 degree slit range shown.
- Remove the 2 nuts that secure the compressor.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EA, p. 120. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.