Daikin Heat Pump: Refrigerant system repair practice (S-100)
Refrigerant system repair practice (S-100) on a Daikin heat pump: Remove the refrigerant before applying heat. There is no pump-down function, so recover all refrigerant through the two service ports on the stop valves.
Applies to: Outdoor units and refrigerant circuit
Common causes of refrigerant system repair practice (s-100)
- Leak or component repair needed on the refrigerant circuit
How to fix refrigerant system repair practice (s-100): step by step
- Recover all refrigerant using the two service ports on the stop valves before applying heat or relocating the unit.
- Never open a system under vacuum.
- Plug or cap all openings as soon as they are made.
- Remove burrs and clean the brazing surfaces with sand cloth or paper.
- Clean the inside of new tubing to remove oils and chips.
- Sweep the tubing with dry nitrogen when brazing to prevent oxides.
- After any repair, replace the liquid line drier, evacuate and charge.
- Use a heat shield and wet rags to protect the serial plate, stop valves, EEV and filters.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin SiUS612209EA service instructions, p. 22. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.