Daikin Heat Pump: Power module check (Check No.22)
Power module check (Check No.22) on a Daikin heat pump: Checks the power module for shorts by measuring resistance to the compressor terminals.
Applies to: Outdoor unit power module and compressor terminals
Common causes of power module check (check no.22)
- Short in the power module (resistance near 0 Ω)
How to fix power module check (check no.22): step by step
- Confirm the voltage between (+) and (-) of the power module is about 0 V before checking.
- Disconnect the compressor harness connector from the outdoor unit PCB. Press the protrusion on the connector to release it.
- Measure resistance between the power module (+) and (-) terminals and the compressor terminals U, V, W, in both polarities, using the table in the manual.
- If the resistance is normal (several kΩ to several MΩ), the power module is OK.
- If the resistance is near 0 Ω or shorted, the power module is NG.
- 09/12 class PCB pin map: pin 24 +, pin 23 U, pin 22 V, pin 21 W, pin 20 -.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin Inverter Pair FTXM-W/V service manual, p. 157. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.