Daikin Heat Pump: Non-condensable in the system
Non-condensable in the system on a Daikin heat pump: Non-condensable gas raises the pressure above what the coil temperature supports.
Applies to: Refrigerant circuit
Common causes of non-condensable in the system
- Air or other non-condensable gas in the system
How to fix non-condensable in the system: step by step
- Shut the system down and let pressures equalize for at least 15 minutes.
- Compare the pressure with the temperature of the coldest coil, where most refrigerant collects.
- If the pressure corresponds to a higher temperature than the coil, non-condensable is present.
- Remove the charge, replace or install the liquid line drier, evacuate and recharge.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 23. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.