Daikin Heat Pump: Low-voltage or over-voltage detection: troubleshooting flow (continued)
Low-voltage or over-voltage detection: troubleshooting flow (continued) on a Daikin heat pump: Flowchart for the power supply check that follows section 4.8. The code number for this flow is not printed on these pages. Page 112 text is jumbled, so the order below is approximate. Verify the sequence against the full flowchart before relying on it.
Applies to: Inverter pair wall mounted FTXM-W/V, outdoor unit power supply
Common causes of low-voltage or over-voltage detection: troubleshooting flow (continued)
- Power supply voltage outside tolerance
- Loose or disconnected harness
- Electrical noise or disturbance on the supply
- Failed indoor or outdoor PCB
- Outdoor fan motor fault
How to fix low-voltage or over-voltage detection: troubleshooting flow (continued): step by step
- Turn off the power switch before connecting or disconnecting any connector.
- Reconnect any loose or disconnected harness.
- Check the supply voltage. It must be within ±10% of the rated value.
- Correct the power supply if voltage is out of range.
- Turn the power off for at least 30 seconds before turning it on again.
- Turn the power on and check whether the system restarts. Repeat a few times.
- If the error returns within 3 minutes of power-on, replace the indoor unit PCB (control PCB).
- Check the outdoor fan. If it does not turn smoothly, replace the outdoor fan motor and the outdoor unit PCB (main PCB).
- If the fault persists, replace the outdoor unit PCB (main PCB).
- Check for longer-term disturbance factors such as noise or power supply distortion.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin FTXM-W/V service manual SiUS042113EA, p. 112. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.