Daikin Heat Pump: Low voltage communication wiring and thermostat connection
Low voltage communication wiring and thermostat connection on a Daikin heat pump: The unit works in a fully communicating system with a Daikin approved communicating thermostat and communicating indoor unit, using up to four wires. The typical installation uses two data wires between the indoor and outdoor units and four wires between the indoor unit and thermostat (data 1 and 2, R and C). Do not connect power wiring to the communication terminals. Do not attach any wires to the R and C terminals on the outdoor unit. Do not connect more than two wires into a single field terminal. Use 18 AWG, or shielded twisted pair for better reliability. The communicating thermostat finds the indoor and outdoor units when power is applied. Allowable maximum lengths printed are 250 and 125 (unit not legible in extracted text).
Applies to: Communicating system wiring for DX6VS / DZ6VS / DZ6VSA
Common causes of low voltage communication wiring and thermostat connection
- Reversed or loose communication wires causing communication error
- More than two wires in a single terminal
How to fix low voltage communication wiring and thermostat connection: step by step
- Connect data line 1 and data line 2 from the outdoor unit to terminals 1 and 2 on the indoor unit and thermostat.
- Connect indoor C to thermostat C and indoor R to thermostat R. Confirm wires are not reversed.
- Leave the R and C terminals on the outdoor unit unconnected.
- Never connect power wiring to communication terminals 1, 2, R or C.
- Keep no more than two wires in any single field terminal.
- Curl the end of each lead and strip only to the marked point.
- Confirm each wire stays in its terminal after all connections are made.
- Use a removable plug connector on 3.5-5.0 ton FIT and 3.0-4.0 ton Enhanced Capacity FIT units.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin DX6VS/DZ6VS installation manual (3P731493-1), p. 21-22. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.