Daikin Heat Pump: Indoor fan motor wiring check (Check 03)
Indoor fan motor wiring check (Check 03) on a Daikin heat pump: Checks the indoor DC fan motor wiring and winding for an open or short.
Applies to: Indoor fan motor (DC motor)
Common causes of indoor fan motor wiring check (check 03)
- Loose or bad connector
- Broken or shorted fan motor wire
How to fix indoor fan motor wiring check (check 03): step by step
- Check that the fan motor connector is fully seated.
- Turn the power off.
- Measure resistance between phases U-V and V-W and compare with the fan motor resistance table.
- Replace the fan motor or repair the wiring if a reading is out of range.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin Inverter Pair FTXM-W/V service manual SiUS042113EA, p. 147. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.