Daikin Heat Pump: High voltage wiring and grounding precautions
High voltage wiring and grounding precautions on a Daikin heat pump: Disconnect all power before servicing. Several power sources may be present. Wiring must follow NEC or CEC and local codes. Undersized wire can cause poor performance, damage or fire. Use copper conductors only. Never fit a phase-advancing capacitor, because the unit has an inverter. Do not change protection devices. Do not connect the ground wire to a gas line, sewage pipe, lightning rod or telephone ground.
Applies to: Power supply wiring to the outdoor unit
Common causes of high voltage wiring and grounding precautions
- Undersized wiring
- Phase-advancing capacitor fitted to inverter unit
- Protection devices bypassed or changed
How to fix high voltage wiring and grounding precautions: step by step
- Disconnect all power and check for multiple power sources before servicing.
- Use copper conductors sized per NEC, CEC and local codes.
- Route power and ground through the high voltage port per the wiring diagram.
- Use a round crimp-style terminal on stranded wires, placed up to the insulated part.
- On a single core wire, curl the end of the lead and strip only to the marked point.
- Tighten terminal screws to the torque table value.
- Secure wires so outside force does not reach the terminal board.
- Do not fit a phase-advancing capacitor.
- Do not change protection device settings or fit non-Daikin parts.
- Reconnect all grounding wires, screws, straps, clips, nuts and washers to their original positions after any servicing.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin DX6VS/DZ6VS installation manual (3P731493-1), p. 19-20. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.