Daikin Heat Pump: Heat exchanger removal (1.5 to 3.0 ton)
Heat exchanger removal (1.5 to 3.0 ton) on a Daikin heat pump: Removal of the outdoor coil heat exchanger on 1.5 to 3.0 ton HP and AC units. The brazed joints are heated, so protect the surroundings first.
Applies to: 1.5 to 3.0 ton HP & AC outdoor units
How to fix heat exchanger removal (1.5 to 3.0 ton): step by step
- Remove the old putty first, since it can burn during brazing.
- Put a protective sheet or steel plate in place so the brazing flame cannot reach nearby parts.
- Remove the suction grille (1 screw).
- Remove 4 screws and take off the left side plate.
- Heat the brazed joints and remove the heat exchanger.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 104. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.