Daikin Heat Pump: Four-way valve performance check (Check 13)
Four-way valve performance check (Check 13) on a Daikin heat pump: Checks the four-way valve coil and its drive voltage on S80 during heating start.
Applies to: Four-way valve coil and S80 drive
Common causes of four-way valve performance check (check 13)
- Open or shorted four-way valve coil
- Faulty four-way valve
- Faulty outdoor unit main PCB drive
How to fix four-way valve performance check (check 13): step by step
- Start heating operation.
- Check the four-way valve coil resistance. If it is not 440 to 750 Ω, replace the coil.
- Measure voltage at S80 with the compressor on. If it reads 0 VDC, check the drive circuit and replace the main PCB if needed.
- Check that S80 reads 120 to 380 VDC for about 3 seconds after compressor start, then drops to about 10 to 24 VDC. If not, replace the main PCB.
- If the coil is good and voltage is correct but the valve still fails, replace the four-way valve.
- Coil continuity check: cooling or dry mode shows no continuity; heating mode shows continuity.
- Caution: wait 30 seconds or more after turning the power off before turning it back on.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin Inverter Pair FTXM-W/V service manual SiUS042113EA, p. 149. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.