Emergency mode overview (when wiring or thermostat has failed) on a Daikin heat pump: Emergency mode is a temporary fallback for when thermostat or indoor-to-outdoor communication cannot be fixed right away. It runs heating or cooling without the communication wires or thermostat. It does not hold a room setpoint, so room temperature depends on the building load. Once wiring or the thermostat is fixed, turn emergency mode off and put the outdoor and indoor units back to normal operation. Emergency mode can be used for these codes if the equipment cannot be fixed immediately: outdoor E51 and Ed2, and EEV indoor E76, E77 and E78. Power cycling may clear those codes but does not fix the cause. In emergency mode the thermostat status menu and outdoor 7-segment displays show no operating status, and the EEV indoor 7-segment display shows EE.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: DX6VS/DZ6VS outdoor with DFVE/CAPE/CHPE EEV units

Common causes of emergency mode overview (when wiring or thermostat has failed)

  • Broken or disconnected thermostat communication wires (1, 2, R, C)
  • Failed thermostat
  • Outdoor to indoor communication failure

How to fix emergency mode overview (when wiring or thermostat has failed): step by step

  1. Turn off power to all equipment before setting or wiring emergency mode.
  2. Limit emergency operation to a short, temporary fallback.
  3. After repair, set all emergency DIP switches back to factory default and restore the thermostat wiring.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Daikin Heat Pump codes

Source: Daikin SiUS612209EA service instructions, p. 32. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.