Daikin Heat Pump: Electronic expansion valve check (Check 12)
Electronic expansion valve check (Check 12) on a Daikin heat pump: Checks the EV coil and its connector and wiring.
Applies to: Electronic expansion valve, 5P and 6P connector models
Common causes of electronic expansion valve check (check 12)
- Loose EV connector
- Open EV coil
- Faulty outdoor unit main PCB
How to fix electronic expansion valve check (check 12): step by step
- Check that the EV connector is fully connected to the PCB.
- Turn the power off and back on. Listen for the EV latching sound.
- If there is no latching sound, disconnect the connector and check continuity.
- On a 5P connector, check continuity between pins 5-1, 5-2, 5-3 and 5-4. On a 6P connector, check pins 6-1, 6-2, 6-3 and 6-4.
- If a pair has no continuity, the EV coil is faulty.
- If continuity is found on the coil, the outdoor unit main PCB is faulty.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin Inverter Pair FTXM-W/V service manual SiUS042113EA, p. 148. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.