Daikin Heat Pump: Cooling analysis chart

Updated · by Aurora Star Tech Inc.

Cooling analysis chart on a Daikin heat pump: Use the readings to find the likely cause. Normal outdoor range for cooling analysis is 67-115 F. Normal indoor range is 65-85 F. Readings that fall outside the limits point to the causes below.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: DX6VS/DZ6VS outdoor unit, cooling mode

Common causes of cooling analysis chart

  • Discharge temperature above 200 F or below 105 F
  • Discharge superheat above 70 F or below 20 F
  • High pressure above 490 psig or below 255 psig
  • Outdoor SSV superheat above 20 F or below 4 F
  • Low pressure above 185 psig or below 100 psig
  • Repeated stop/start, weak cooling, no switch cooling, noise, or stop operation
  • Stop valve not fully open, line set restriction or too long, blocked filter-dryer, EEV or sensor faults, dirty coils, recirculation, out-of-range ambient, non-condensable gas, fan or compressor failure, over or under charge, leak, control board failure, low indoor CFM

How to fix cooling analysis chart: step by step

  1. Fully open the liquid and gas stop valves.
  2. Check the line set for restriction and length. Change OD position if needed.
  3. Replace the filter-dryer if it is blocked.
  4. Check the EEV, sensors and coils. Repair or replace as needed.
  5. Re-arrange OD or ID position if recirculation is present.
  6. Clean dirty outdoor or indoor heat exchangers.
  7. Recover refrigerant, evacuate and recharge if non-condensable gas is present.
  8. Recover part of the charge if overcharged; test for leaks and add refrigerant if undercharged.
  9. Specify and repair any leak point.
  10. Check airflow trim and the ID fan motor if CFM is low.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Daikin Heat Pump codes

Source: Daikin DX6VS/DZ6VS outdoor unit installation manual, p. 41. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.