Daikin Heat Pump: Cooling analysis chart: possible causes and remedies
Cooling analysis chart: possible causes and remedies on a Daikin heat pump: Use the cooling analysis chart when the unit shows high or low discharge temperature, pressure or superheat, repeated stop/start, weak cooling, no cooling, or noise. Normal cooling range: outdoor 67-115 F, indoor 65-85 F.
Applies to: DX6VS / DZ6VS heat pump in cooling
Common causes of cooling analysis chart: possible causes and remedies
- Liquid stop valve not fully open
- Gas stop valve not fully open
- Line set restriction
- Line set too long
- Blocked filter-dryer
- Indoor EEV coil failure
- Indoor EEV failure
- Outdoor solenoid valve coil failure
- Outdoor solenoid valve failure
- High pressure switch failure
- Pressure sensor failure
- Outdoor suction thermistor failure
- Outdoor discharge thermistor failure
- Outdoor coil thermistor failure
- Outdoor air thermistor failure
- Outdoor air recirculation
- Indoor air recirculation
- Dirty outdoor heat exchanger
- Dirty indoor heat exchanger
- Outdoor ambient temperature too high or too low
- Indoor return air temperature too high or too low
- Non-condensable gas in system
- Outdoor fan motor failure
- Overcharge
- Undercharge
- Refrigerant leak
- Outdoor control board failure
- Indoor unit failure
- Compressor failure
- Compressor and gas furnace running at the same time
- Cooling loop not attached to cold plate
- Cooling loop grease insufficient
- Low indoor CFM
How to fix cooling analysis chart: possible causes and remedies: step by step
- Fully open the liquid stop valve.
- Fully open the gas stop valve.
- Check the line set for restriction; check line set length and change outdoor position if needed.
- Replace the filter-dryer if blocked.
- Check the indoor EEV coil connection to the control board; repair or replace if needed.
- Check the indoor EEV; replace or repair if needed.
- Check the outdoor solenoid valve coil connection; repair or replace if needed.
- Check the outdoor solenoid valve; replace or repair if needed.
- Check the high pressure switch resistance; replace if needed.
- Check the pressure sensor resistance and connections; replace if needed.
- Check the outdoor suction, discharge, coil and air thermistors for resistance and connections; replace if needed.
- Re-arrange the outdoor unit position if air is recirculating.
- Re-arrange the indoor unit position if air is recirculating.
- Clean the outdoor heat exchanger.
- Clean the indoor heat exchanger.
- Recover refrigerant, evacuate the pipe and recharge if non-condensable gas is present.
- Replace the outdoor fan motor if it has failed.
- Recover part of the charge if overcharged.
- Test for leaks and add refrigerant if undercharged.
- Find and repair the leak point.
- Replace the outdoor control board if it has failed.
- Replace the indoor unit if it has failed.
- Replace the compressor if it has failed.
- Attach the cooling loop to the cold plate.
- Add grease to the cooling loop if insufficient.
- Check airflow trim and indoor fan motor; repair or replace if needed.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin DX6VS / DZ6VS service instructions SiUS612209EA, p. 12. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.