Daikin Heat Pump: Compressor wiring and thermistor removal (3.5 to 5.0 ton HP)

Updated · by Aurora Star Tech Inc.

Compressor wiring and thermistor removal (3.5 to 5.0 ton HP) on a Daikin heat pump: Disconnecting compressor power and removing the outdoor air, outdoor coil, defrost and suction pipe thermistors on heat pump models.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: 3.5 to 5.0 ton HP outdoor units

How to fix compressor wiring and thermistor removal (3.5 to 5.0 ton hp): step by step

  1. Disconnect the PS connector (X17A).
  2. Disconnect the compressor leads at U, V and W, and release them from the hooks.
  3. Remove the outdoor air thermistor, outdoor coil thermistor and defrost thermistor. Thermistor positions differ between 3.5/4.0 ton and 5.0 ton units.
  4. Cut the 2 clamps and remove the insulation tube.
  5. Remove the suction pipe thermistor.
  6. On reassembly, position the slit in the insulation tube opposite the suction pipe thermistor.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Daikin Heat Pump codes

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, pp. 111-112. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.