Daikin Heat Pump: Compressor insulation resistance test (S-17A)
Compressor insulation resistance test (S-17A) on a Daikin heat pump: The inverter on the outdoor control board reads the position signal from the UVW lines to the compressor. Use this test when the system reports a compressor fault.
Applies to: Outdoor units DX6VS / DZ6VS, 1.5-5.0 ton
Common causes of compressor insulation resistance test (s-17a)
- Insulation breakdown between compressor terminal and housing
- Wiring error on UVW terminals
How to fix compressor insulation resistance test (s-17a): step by step
- Disconnect all power.
- Remove the leads from the compressor terminals. Follow the S-17 warnings before removing the terminal cover.
- Check the UVW wiring connection on the compressor terminals (label on top of compressor).
- Measure insulation resistance between the compressor terminal and unpainted refrigerant piping.
- If the reading is anything other than infinity, replace the compressor.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin SiUS612209EA service instructions, p. 20. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.