Daikin Heat Pump: Compressor ground test
Compressor ground test on a Daikin heat pump: Use when a breaker or fuse has tripped. A trip indicates an electrical fault that must be found. The circuit protective device rating must match the nameplate.
Applies to: Compressor leads on outdoor unit
Common causes of compressor ground test
- Compressor winding grounded to housing
- Damaged lead wires or insulation
How to fix compressor ground test: step by step
- If a breaker or fuse trips, the terminal cover in place allows one reset or fuse replacement only. If it trips again, do not reset.
- Disconnect all power, making sure all legs are open.
- Without removing the terminal cover, disconnect the three compressor leads at the nearest point.
- With the ohmmeter on the highest resistance scale (R x 10,000 or higher), check each lead to ground (for example an unpainted tube on the compressor).
- If a ground is indicated, remove the terminal cover and inspect for loose leads or broken insulation.
- If nothing is visible, remove the leads at the compressor terminals carefully, then retest each terminal to ground.
- If ground is still indicated, replace the compressor. Reading should be infinity.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 21. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.