Daikin Heat Pump: Compressor ground test (S-17B)
Compressor ground test (S-17B) on a Daikin heat pump: A tripped fuse or breaker means an electrical problem exists. Check that the breaker or fuse rating matches the nameplate before resetting.
Applies to: Outdoor units DX6VS / DZ6VS
Common causes of compressor ground test (s-17b)
- Compressor winding grounded to housing
- Damaged lead insulation at the compressor
How to fix compressor ground test (s-17b): step by step
- If a fuse or breaker tripped, replace the fuse or reset the breaker one time only. If it trips again, do not reset.
- Disconnect all power and make sure all legs are open.
- Do not remove the terminal cover. Disconnect the three compressor leads at the nearest point.
- Using an ohmmeter on the highest resistance scale (R x 10,000 or higher), check each lead to ground (such as an unpainted tube).
- If a ground is indicated, remove the terminal cover and check for loose leads or broken insulation.
- If no visible fault, remove the leads at the compressor terminals and retest each terminal to ground.
- If there is any reading, the compressor is defective. Replace it. Expect infinity.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin SiUS612209EA service instructions, p. 21. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.