Daikin Heat Pump: Cold climate outdoor unit location
Cold climate outdoor unit location on a Daikin heat pump: Install the unit so snow and drain water cannot block the coil or freeze the base.
Applies to: Outdoor units in areas with snow or low ambient
How to fix cold climate outdoor unit location: step by step
- Mount the unit on a field-supplied stand so the bottom frame is more than 19 3/4 in. (500 mm) above expected snowfall.
- Fit a snow hood and snow visor (field supplied).
- Do not put the unit where snowdrift forms.
- Use a drain pan heater where outdoor air drops below 32°F (0°C) for more than 12 hours in a row, or in high humidity or heavy snow areas.
- Do not use a concentrated drain pipe. Use only the existing drain holes.
- Remove the rear inlet grille so snow does not build up on the rear fins.
- Keep the suction side facing a wall and do not expose it directly to wind. Use a baffle plate on the discharge side if wind is a problem.
- In heavy snowfall areas, raise the unit on a pedestal or build a large canopy.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin DX6VS/DZ6VS outdoor unit installation & service reference, p. 9. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.