Daikin Heat Pump: Checking the high pressure switch

Updated · by Aurora Star Tech Inc.

Checking the high pressure switch on a Daikin heat pump: The high pressure switch opens the control circuit on abnormally high discharge pressure, before the compressor overloads. It does not reset automatically.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: High pressure switch on the outdoor unit control circuit

Common causes of checking the high pressure switch

  • Open switch contacts
  • Broken or loose wiring at the PCB connection

How to fix checking the high pressure switch: step by step

  1. Disconnect power and wait for the high voltage to be cleared.
  2. Remove the wire on the PCB side of the switch.
  3. Use an ohmmeter across the PCB-side switch terminals.
  4. If the reading is not continuous, the circuit is open. Replace the switch if necessary.
  5. After a trip, turn main power off to reset the switch.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Daikin Heat Pump codes

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 16. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.