Daikin Heat Pump: Checking compressor efficiency

Updated · by Aurora Star Tech Inc.

Checking compressor efficiency on a Daikin heat pump: Low efficiency means the compressor cannot pump vapor properly. Confirm the charge is correct before condemning the compressor.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Outdoor unit compressor

Common causes of checking compressor efficiency

  • Broken or damaged compressor

How to fix checking compressor efficiency: step by step

  1. Attach gauges to the high and low sides.
  2. Start the system and run CHARGE MODE.
  3. If the readings show low high-side pressure, high low-side pressure, low temperature difference across the coil, and low compressor amp draw, and the charge is correct, replace the compressor.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Daikin Heat Pump codes

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 22. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.