Daikin Heat Pump: Check for non-condensables (S-114)
Check for non-condensables (S-114) on a Daikin heat pump: Non-condensables are gas trapped in the system that does not condense. Check when pressures look wrong.
Applies to: Outdoor units DX6VS / DZ6VS
Common causes of check for non-condensables (s-114)
- Air or other non-condensable gas in the refrigerant circuit
How to fix check for non-condensables (s-114): step by step
- Shut the system down and let pressures equalize for at least 15 minutes.
- Compare the pressure with the saturation temperature of the coldest coil, since most refrigerant collects there.
- If the pressure reads a higher temperature than the coil, non-condensables are present.
- Remove the charge, replace or install a liquid line drier, evacuate and recharge.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin SiUS612209EA service instructions, p. 23. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.