Daikin Heat Pump: Check compressor efficiency (S-104)
Check compressor efficiency (S-104) on a Daikin heat pump: Low compressor efficiency means the compressor cannot pump vapor well. Confirm the charge is correct before condemning the compressor.
Applies to: Outdoor units DX6VS / DZ6VS
Common causes of check compressor efficiency (s-104)
- Broken or damaged compressor
- Incorrect refrigerant charge (check first)
How to fix check compressor efficiency (s-104): step by step
- Attach gauges to the high and low side of the system.
- Start the system and run CHARGE MODE.
- If the charge is correct and the readings show low high-side pressure, high low-side pressure, low temperature difference across the coil, and low compressor amp draw, the compressor is faulty. Replace it.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin SiUS612209EA service instructions, p. 22. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.